HCH8s-100/4P DC Contactor
Model:HCH8s-100
Rated Current:100A
Specification:4NO, 4NC, 3NO1NC, 2NO2NC
Coil Voltage: AC/DC24V
Email:hofwge@outlook.com
Views:
Date:2022-03-03
next previous

Details

Scope of application

HCH8s Modular Contactor (also known as analog contactors and architectural contactors) are mainly used in power systems with AC 50Hz/60Hz, rated working voltage up to 400V and rated working current up to 100A. They are used as remote switches and control circuits in AC-1 and AC-7a (non-inductive or low-inductive loads, resistance furnaces, household appliances and similar low-inductive loads). It can also be used to control the load of household motor. Modular Contactors cant't be used in break short-circuit currents, so appropriate short-circuit protective appliances (such as small circuit breakers) should be selected when using them. It meets the standard IEC 61095.

HCH8s contactor can expand auxiliary control, protection and indication functions.

HCH8s Modular Contactor is a kind of control device used for long distance connection and disconnection of inductionless or low inductive load, resistance furnace, household appliances and similar low inductive load, household motor, etc.

HCH8s Modular Contactor are mainly used in homes, hotels, apartments, office buildings, public buildings, shopping malls, gymnasiums and other places to achieve automatic control functions.


Product Features

1, Modular Control electrical appliances, novel structure, small size.

2, Theinstallation of the track, the size of the module, the use of safety, can be combined with the small circuit breaker installed in the control lighting box.

3, The use of high-quality insulation materials, greatly improving the safety.

4, Beautiful appearance, with working status indicator window.

5, No noise,suitable for hotels,hospitals and other places.


Model and its meaning

Normal working conditions

Ambient air temperature: The upper limit of ambient air temperature is + 60℃ and the lower limit is - 5℃. When the AC contactor is installed in the distribution box, spacers must be assembled on both sides to facilitate heat dissipation. Elevation: The altitude of the installation site shall not exceed 2000m.

Atmospheric Conditions: When the installation temperature is + 60℃, the relative humidity of the air does not exceed 50%. Higher relative humidity can be allowed at lower temperatures, such as + 20℃ up to 90%. Special measures should be taken for occasional condensation due to temperature changes.

Pollution grade: Grade II.

Installation Category: II.

Installation method: TH35-7.5 typeguide rail is used for installation. There is no significant impact and vibration at the installation site. It is installed vertically. The inclination between the installation surface and any direction is not more than 5 degrees.


Main technical parameters

Quota system

A) Eight-hour working system: This working system is the basic working system. The agreed free air heating current Ith of the Modular Contactor is determined by this working system.

B) Intermittent periodic working system: The operating frequency of the AC contactor is 30 times/h and the load factor is 40%.

Action (operation) condition

In the ambient air temperature range of - 5 +60℃, when the suction coil of the contactor is applied with a quota to control the power supply voltage Us so as to heat it to a stable state, the contactor should be reliably closed at any voltage in the range of (85%~110%) Us, and released and disconnected between 75% and 20% of the rated control power supply voltage Us.

Product life

Mechanical life: The mechanical life of modular contactor is not less than 1 million times.

Electrical life: The electrical life of analog contactor is not less than 100,000 times.

Specifications

16A

20A

25A

40A

63A

100A

Rated current

AC-7a

16

20

25

40

63

100

AC-7b

6

7

8.5

15

20

30

Agreed heating current Ith(A)

25

25

25

63

63

100

Rated insulation voltage Ui(V)

500

Rated operating voltage Ue(V)

250V(1P/2P) , 400V(3P/4P)

Number of main contacts

1P

1NO1NC

2P

1NO1NC, 2NO, 2NC

3P

3NO, 3NC

4P

2NO2NC, 3NO1NC, 4NO, 4NC

Control power

AC-7a

230V

3.5

4.5

5.5

9

14

22

400V

6.5

8

10

16

25

38

AC-7b

230V

1.4

1.6

2

3.5

4.5

6.5

400V

2.4

2.8

3.4

6

8

11

Electrical life(times)

10ten thousand

Mechanical life(times)

100ten thousand

Maximum number of switching operations per hour

30

Maximum number of switching operations per day

100

Quota control power supply voltage Us(V)

AC24/50Hz, AC230/50Hz

frequency

50Hz/60Hz

Class of pollution

2

Rated impulse withstand voltage(Uimp)

2.5kV(4kV--12/24/48VAV)

Protection level
(IEC60529)

Contactor body

IP20

Installed in distribution box

IP40

working temperature

-5℃~+60℃

Storage temperature

-40℃~+70℃

Hygrothermal resistance(IEC60068.1)

2-class(At 55℃,Relative humidity is 95%)

ELSV(Ultra-low Safety Voltage) 12/24/48 VAC

Product control meets the requirements of SELV (Safe Ultra-Low Voltage)

Note: When the contactor is installed in the distribution box, spacers must be assembled on both sides to facilitate heat dissipation.

Working principle

When the coil is electrified, the coil current generates magnetic field, which generates enough electromagnetic suction to overcome the reaction force, and the armature is sucked in to make the contact connected. When the coil voltage disappears or the coil voltage will be low to a certain value, that is, when the so-called release voltage, the magnetic flux generated by the armature end surface decreases, the electromagnetic suction begins to be smaller than the reaction force produced by the reaction spring and the contact spring. The armature of the contactor is released under the action of this reaction force, leaving the yoke, and the contact breaks off immediately.

Selection of 50Hz Modular Contactor

50Hz Selection of Modular Contactor

Type

Contactor

Manual operating contactor

Rated current A

16

25

40

63

100

25

40

63

Enclosure

Attachable contactor

HCH8s Indication accessories

Control attachment through yellow clip

Control attachment through yellow clip

●(Contactor 230V-50Hz)

●(Contactor 230V-50Hz)














HCH8s Selection of Modular Contactor

Operation (manual operation of contactor)

Installation diagram

Type

Rated current

Strip length

Circuit

torque

Copper wire

Sketch Map

Hard wire

Flexible or hoop terminal

HCH8s

PZ1:4mm

16-100A

9mm

control loop

0.8Nm

1.5~2.5mm2

2×1.5mm2

1.5~2.5mm2

2×2.5mm

16and25A

Power loop

1.5×6mm2

1~4mm

PZ2:6mm

40A-63A

14mm

3.5Nm

6×25mm2

6~16mm

100A

6×35mm2

6~35mm

HCH8s

PZ1:4m

9mm

-

0.8Nm

1.5×2.5mm2

2×1.5mm2

1.5×2.5mm2

2×2.5mm2

Electrical accessories

Signal class

control class

Enclosure

HCH8s

HCH8s

type

Signal contact

Pulse/Continuous Signal Control

function

●Used to indicate the "on" or "off" status of the

main contacts of contactors

●Connect the contactor to the attachment so that it can be

controlled by two types of commands.

○Pulse commands for local control (input T)

○Continuous signal command for centralized control (input X)

○The last command received has priority

Modular Contactor Wiring diagram

install

●Installed on the right side

●Installed on left side of HCH8s through yellow clip

Use

-

●When the power supply circuit is disconnected:
○<1s:Keep the initial state
○≥5s:reset
○Manual action is restarted for X or T
●Minimum pulse duration:250ms

technical specifications

Control voltage(Ue)

VAC

24...240

230...240

24...48

VDC

24...130

-

Working frequency

Hz

50

Width (multiple of 9mm)

1

2

Auxiliary contact (breaking capacity)

●Minimum:10mA stay 24VDC/AC-COSΦ=1
Maximum:
○5A 240V DC-COSΦ=1
○1A stay130 VDC

-

Contact Points

1 N O +1 N C

-

Working temperature

-5℃~+50℃

Working temperature

-5℃~+50℃

Contactor Power Consumption

HCH8s Household AC contactor-50Hz

Rated current(In)

control voltage
(VAC)(50Hz)

Power waste keep

Suction

maximum power

AC7a

AC7b

1P

25A

8.5A

230...240

2.7VA

9.2VA

1.2W

2P

16A

6A

230...240

2.7VA

9.2VA

1.2W

230...240

2.7VA

9.2VA

1.2W

25A

8.5A

24

3.8VA

15VA

1.3W

230...240

2.7VA

9.2VA

1.2W

230...240

2.7VA

9.2VA

1.2W

40A

15A

220...240

4.6VA

34VA

1.6W

63A

20A

220...240

4.6VA

34VA

1.6W

100A

-

220...240

6.5VA

53VA

2.1W

3P

25A

8.5A

220...240

4.6VA

34VA

1.6W

40A

15A

220...240

6.5VA

53VA

2.1W

63A

20A

220...240

6.5VA

53VA

2.1W

4P

16A

6A

220...240

4.6VA

34VA

1.6W

25A

8.5A

24

4.6VA

34VA

1.6W

220...240

4.6VA

34VA

1.6W

24

4.6VA

34VA

1.6W

220...240

4.6VA

34VA

1.6W

220...240

4.6VA

34VA

1.6W

40A

15A

220...240

6.5VA

53VA

2.1W

220...240

6.5VA

53VA

2.1W

63A

20A

220...240

6.5VA

53VA

2.1W

220...240

6.5VA

53VA

2.1W

220...240

6.5VA

53VA

2.1W

220...240

6.5VA

53VA

2.1W

100A

-

220...240

13VA

106VA

4.2W

HCH8s Manual operation of Modular Contactors-50Hz

Rated current(In)

control voltage
(VAC)(50Hz)

Power waste keep

Suction

maximum power

AC7a

AC7b

2P

25A

8.5A

230...240

2.7VA

9.2VA

1.2W

40A

15A

220...240

4.6VA

34VA

1.6W

63A

20A

220...240

4.6VA

34VA

1.6W

4P

25A

8.5A

220...240

4.6VA

34VA

1.6W

40A

15A

220...240

6.5VA

53VA

2.1W

63A

20A

220...240

6.5VA

53VA

2.1W


Shape and installation dimensions

Installation, use and maintenance

Before installation, technical data of Modular Contactor (such as rated voltage, current, operating frequency, etc.) should be checked.

When installing, it should be installed according to the stipulated conditions. The terminal A1 of the contactor coil should be facing upward and conform to people's visual habits.

Contactors with metal mounting boards should be properly grounded.

The screw of the terminal should be tightened. After checking the correct connection, the main contact should be disconnected several times before it can be put into use.

If abnormal noise is found in the use of Modular Contactors, it may be dirt on the pole surface of the iron core, please wipe the pole surface.

In the use of Modular Contactor, all parts of the product should be inspected regularly. The movable parts should not be jammed and the fasteners should not be loosened. If the parts are damaged, they should be replaced in time.

HCH8s Modular Contactor can be used in large-scale lighting circuit control, public hot water control, geothermal power supply control, automatic curtain rolling control, small motor control and other fields.

All right. In large public places such as hotels, hotels, stations, hospitals and office buildings, all kinds of electrical equipment can be effectively controlled, which can be used as the best terminal execution unit of intelligent building system Pieces.


Application occasion

Bank, Industry and Commerce, Taxation, Telecom, Hospital, Post, Finance Bureau, Labor Bureau, Personnel Bureau, Social Security Bureau, Government One-stop Service Office, Insurance, Vehicle Administration, Transportation

Windows service industries such as administrative bureau, consulate, entry-exit, customs, inspection and quarantine bureau, disease prevention and control center, Technical Supervision bureau, product customer service center, etc.


Matters needing attention

1. Before installation, check whether the Modular Contactor is in conformity with the scope of use and normal working conditions.

2. The connection mode of HCH8s contactor should be correct.

3. HCH8s Modular Contactor should tighten the connection screw when wiring.